Leak DetectionUser GuideLD5200Version 2.3Firmware Version 2.2.1
10 LD5200 User Guide 800.518.1519Figure 4.32 Alarm Management Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
100 LD5200 User Guide 800.518.15195 Modbus Communication5.5 RTU FramingThe example below shows a typical Query/Response from the LD5200 module.Slave
rletech.com LD5200 User Guide 101A PPENDIXCHAPTE R 0UPDATE FIRMWAREA.1 Update the LD5200 Firmware1 Firmware updates are available online at rletech.c
102 LD5200 User Guide 800.518.1519A Update FirmwareThe path and name of the firmware file (.bin) displays in the field to the left of the Browse butt
rletech.com LD5200 User Guide 103A PPENDIXCHA PTER 0EIA-232 INTERFACEThe EIA-232 Interface is used primarily for advanced diagnostic and configuration
104 LD5200 User Guide 800.518.1519B EIA-232 Interface5 Repeat step 4 to change the Subnet Mask and Default Route (gateway), if needed, using the comm
rletech.com LD5200 User Guide 105B EIA-232 InterfaceB.4 Other Main Menu FunctionsThe remainder of the functions available from the Main Menu of the
106 LD5200 User Guide 800.518.1519B EIA-232 Interface
rletech.com LD5200 User Guide 107A PPENDIXCH APTER 0PREVENTIVE MAINTENANCEFollow these steps monthly to test the system and ensure that the control pa
108 LD5200 User Guide 800.518.1519C Preventive Maintenance
rletech.com LD5200 User Guide 109A PPENDIXCHAP TER 0TROUBLESHOOTINGD.1. Troubleshooting Problems with the LD5200Problem ActionControl Panel will not P
Tablesrletech.com LD5200 User Guide 111 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
110 LD5200 User Guide 800.518.1519D TroubleshootingCable Break Alarm 1 Verify that the leader cable is plugged into terminal block TB2, and the wires
rletech.com LD5200 User Guide 111D TroubleshootingControl Panel not Calculating Proper Leak Distance 1 Check the distance on the cable run to verify
112 LD5200 User Guide 800.518.1519D TroubleshootingD.2. Troubleshooting Sensing CableNote Contamination and/or physical damage to the cable is not c
rletech.com LD5200 User Guide 113D TroubleshootingHow do I clean the cable?Use a mild detergent solution - 1 cap full of Dawn liquid dishwashing dete
114 LD5200 User Guide 800.518.1519D Troubleshooting
rletech.com LD5200 User Guide 115A PPENDIXCHAPTE R 04-20MA OUTPUT TESTINGThe LD5200’s 4-20mA output is loop powered and tested by the manufacturer. Th
116 LD5200 User Guide 800.518.1519E 4-20mA Output Testing10Turn off power to the LD5200.11Remove the resistor and wires from the plug and reattach an
rletech.com LD5200 User Guide 117A PPENDIXCHA PTER 0TECHNICAL SPECIFICATIONSTable F.1Technical SpecificationsPower 100-240VAC @ 500mA Max, 50/60 HzInp
118 LD5200 User Guide 800.518.1519F Technical SpecificationsEIA-485 Modbus RTU, Master & Slave; BACnet MS/TP; N2, SlaveEIA-232 Terminal emulation
12 LD5200 User Guide 800.518.1519Table 5.2 Read Output Registers Packet Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87Table
rletech.com LD5200 User Guide 13C HAPTERCHAPT ER 0PRODUCT OVERVIEW1.1 DescriptionThe LD5200 is a distance-read leak detection controller. It can opera
14 LD5200 User Guide 800.518.15191 Product Overview1.2.2 Distance-Read Leak DetectionWhen the LD5200’s circuitry measures a current in excess of the
rletech.com LD5200 User Guide 15C HAPTERCHAPT ER 0INSTALLATION2.1 Prepare for InstallationTo install the LD5200, you’ll need the following supplies:I
16 LD5200 User Guide 800.518.15192 Installation2.2 Mount the LD5200The LD5200 is a wall mounted device. Using the wall mount kit (included), mount th
rletech.com LD5200 User Guide 172 InstallationFigure 2.2LD5200 Physical Connections and SwitchesTB4 - (2) Form C Leak Relay OutputsTB3 - Form C Maint
18 LD5200 User Guide 800.518.15192 Installation2.3.1 TB1: 4-20mA OutputThe 4-20mA analog output allows the LD5200 to communicate with a 4-20mA loop p
rletech.com LD5200 User Guide 192 InstallationConnect the alarm relay wires to TB4 as follows:TB4-1 Leak alarm normally open (NO)TB4-2 Leak alarm com
2 LD5200 User Guide 800.518.1519Copyright and Trademark Notices© Raymond & Lae Engineering, Inc. 2012. All rights reserved. RLE® is a registered t
20 LD5200 User Guide 800.518.15192 InstallationTB6 (bottom row) EIA-485 port 2TB6-4 A (+)TB6-5 B (-)TB6-6 Shield2.3.8 SW2: TB6 Port 2 (Bottom Row) T
rletech.com LD5200 User Guide 212 Installation2.4 Connect the SeaHawk Sensing CableIMPORTANT To avoid faulty leak detection readings, connect a mini
22 LD5200 User Guide 800.518.15192 Installation♦ The J-clip’s adhesive backing does not work well on porous concrete floors. RLE recommends using a d
rletech.com LD5200 User Guide 232 Installation4 When the LD5200 powers up, diagnostics are performed. The program code is verified. Once the diagnost
24 LD5200 User Guide 800.518.15192 Installation2.7 Test the SystemNote If the LD5200 is already connected to a BMS or NMS, notify monitoring personne
rletech.com LD5200 User Guide 252 Installation2.8 Calibrate Cable ResistanceDistance-read leak detection systems are resistance-based. RLE’s orange
26 LD5200 User Guide 800.518.15192 Installation5 To calculate the most accurate resistance value for the system, divide the reported cable length by
rletech.com LD5200 User Guide 272 Installation2.9 Configure Security SettingsThe LD5200 allows users to create a user name for web interface access a
28 LD5200 User Guide 800.518.15192 Installation
rletech.com LD5200 User Guide 29C HAPTERCHAP TER 0LCD TOUCH SCREEN INTERFACEThe LD5200’s LCD touch screen accommodates basic device configuration and
rletech.com LD5200 User Guide 3Product RegistrationProduct registration helps RLE Technologies inform owners of:• Product upgrades• Firmware enhanceme
30 LD5200 User Guide 800.518.15193 LCD Touch Screen Interface3.1 Main MenuWhen the LD5200 powers up, diagnostics are performed. The boot ROM and flas
rletech.com LD5200 User Guide 313 LCD Touch Screen Interface3.3 Alarms ButtonThe Alarms option allows users to display current alarms and alarm histo
32 LD5200 User Guide 800.518.15193 LCD Touch Screen Interface3.3.1 HistoryPush this button to display the alarm history. The LD5200 logs the last 102
rletech.com LD5200 User Guide 333 LCD Touch Screen Interface3.4 Status ButtonThe Status button allows you to view current controller status informati
34 LD5200 User Guide 800.518.15193 LCD Touch Screen InterfaceThis menu features four buttons: Next, Previous, System, and Return:Button FunctionAddit
rletech.com LD5200 User Guide 353 LCD Touch Screen Interface3.4.1 System ButtonView the system status information for the selected controller. Here y
36 LD5200 User Guide 800.518.15193 LCD Touch Screen Interface3.5 Setup ButtonThe Setup button provides access to a wide variety of settings, includin
rletech.com LD5200 User Guide 373 LCD Touch Screen Interface3.5.1 Leak SettingsLeak Settings allows you to fine tune the leak detection options avail
38 LD5200 User Guide 800.518.15193 LCD Touch Screen InterfaceContamination Alarm DelayThe amount of time that passes between the time a contamination
rletech.com LD5200 User Guide 393 LCD Touch Screen InterfaceLatching Alarms A non-latching alarm resets itself once a detected leak or contamination
4 LD5200 User Guide 800.518.1519RLE Product WarrantySeller warrants to the Ultimate Purchaser (the purchaser who buys for use and not for resale) that
40 LD5200 User Guide 800.518.15193 LCD Touch Screen Interface3.5.2 Virtual ZoneA virtual zone is a labeled reference point in a leak detection system
rletech.com LD5200 User Guide 413 LCD Touch Screen Interface3.5.3 Slave ZoneSlave zones are secondary physical controllers that report to the LD5200.
42 LD5200 User Guide 800.518.15193 LCD Touch Screen Interface3.5.4 4-20mA OutputThe 4-20mA output only reports up to 5,000 feet of sensing cable.Opti
rletech.com LD5200 User Guide 433 LCD Touch Screen Interface3.5.5 Preventative MaintenancePreventative maintenance keeps a leak detection system runn
44 LD5200 User Guide 800.518.15193 LCD Touch Screen Interface3.5.6 System SettingsA variety of settings are available to make your LD5200 easy to ide
rletech.com LD5200 User Guide 453 LCD Touch Screen Interface3.5.7 EIA-485 / Modbus / N2If the LD5200 will be communicating via the EIA-485 port, con
46 LD5200 User Guide 800.518.15193 LCD Touch Screen Interface3.5.8 BacnetThe LD5200 can communicate via BACnet. BACnet allows building automation and
rletech.com LD5200 User Guide 47C HAPTERCHAP TER 3WEB INTERFACEThe LD5200’s LCD accommodates most device control and configuration. For more in-depth
48 LD5200 User Guide 800.518.15194 Web InterfaceThe home page also provides annunciation for active alarms.Figure 4.2LD5200 Web Interface Home Page w
rletech.com LD5200 User Guide 494 Web Interface4.3 ConfigurationThe Configuration link provides access to a series of sub-menus from which users can
Contentsrletech.com LD5200 User Guide 51 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50 LD5200 User Guide 800.518.15194 Web Interface4.3.1 LeakUse the Leak Configuration page to fine tune system variables, including leak and contamina
rletech.com LD5200 User Guide 514 Web InterfaceOption DescriptionLeak Trip Point The threshold for the amount of water required to trigger a leak ala
52 LD5200 User Guide 800.518.15194 Web InterfaceResistance Per Foot The resistance per foot (or meter) of cable determines the LD5200’s ability to ac
rletech.com LD5200 User Guide 534 Web InterfaceSet Cable Relay Button - Use to troubleshoot the controller, this button simulates 8060 ohms of leak d
54 LD5200 User Guide 800.518.15194 Web Interface4.3.2 Virtual ZoneA virtual zone is a labeled reference point in a leak detection system. A virtual z
rletech.com LD5200 User Guide 554 Web Interface4.3.3 Slave ControllerThe LD5200 can act as a Modbus or Bacnet IP master for other RLE leak detection
56 LD5200 User Guide 800.518.15194 Web Interface4.3.4 Slave ZonesIf you have designated controllers on the Slave Configuration page, then use this pa
rletech.com LD5200 User Guide 574 Web Interface4.3.5 Network/IPThe Network/IP page displays the assigned MAC address and allows users to configure co
58 LD5200 User Guide 800.518.15194 Web Interface4.3.6 Network StatisticsThe Network Statistics link displays a snapshot of the most recent network in
rletech.com LD5200 User Guide 594 Web Interface4.3.7 WebUse this page to establish passwords and a username for the web interface, and to customize t
6 LD5200 User Guide 800.518.1519Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60 LD5200 User Guide 800.518.15194 Web Interface4.3.8 MapThe LD5200 allows users to upload up to 10 maps of their facilities and populate them with l
rletech.com LD5200 User Guide 614 Web InterfaceThe LD5200 allows users to upload 10 maps, and make all 10 of the maps interactive. Use the drop down
62 LD5200 User Guide 800.518.15194 Web InterfaceMap TypeOnly available on Map 1Distance Read - the traditional map overlay, use this option to plot p
rletech.com LD5200 User Guide 634 Web InterfaceSeveral options on this page fall above the gray line that separates the image upload section of the p
64 LD5200 User Guide 800.518.15194 Web Interface2 Locate and select the map file you have previously created and saved. Click the Open button. The pa
rletech.com LD5200 User Guide 654 Web InterfaceThroughout the mapping process, you will use a set of crosshairs to designate the location of your map
66 LD5200 User Guide 800.518.15194 Web Interfaceat the top of the webpage, type 0 to set the reference point for the beginning of the cable run.Figur
rletech.com LD5200 User Guide 674 Web Interfacewith their distance measurements. This demonstrates what the coordinates will look like when an alarm
68 LD5200 User Guide 800.518.15194 Web InterfaceIf any coordinates need to be adjusted, you can fine tune them through the Map Alarm Coordinates - Te
rletech.com LD5200 User Guide 694 Web Interface4.3.8.4 Viewing the MapOnce you have given the map a title, the title appears on the Home page as an a
rletech.com LD5200 User Guide 7Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
70 LD5200 User Guide 800.518.15194 Web Interface4.3.10 NTPNTP, or Network Time Protocol, is used to synchronize clocks of computer systems. NTP synch
rletech.com LD5200 User Guide 714 Web InterfaceDST Begin Date Set the day DST begins at your location.Default setting: Second Sunday - MarchDST End D
72 LD5200 User Guide 800.518.15194 Web Interface4.3.11 Email-SMTP/DNSConfigure email and SMTP settings through this page.Figure 4.28Email-SMTP/DNS Co
rletech.com LD5200 User Guide 734 Web InterfaceSecondary DNS ServerEnter the IP address for the secondary DNS server, as provided by your internet se
74 LD5200 User Guide 800.518.15194 Web Interface4.3.12 SNMP/SyslogUse this page to configure the LD5200 for SNMP communications.Figure 4.29SNMP/Syslo
rletech.com LD5200 User Guide 754 Web InterfaceSelect Snmp Trap TypeSelect the appropriate trap type from the drop-down menu. SNMP V3 is available as
76 LD5200 User Guide 800.518.15194 Web Interface4.3.13 EIA-485 Port/Modbus/N2If the LD5200 will communicate via the EIA-485 port, configure the neces
rletech.com LD5200 User Guide 774 Web InterfaceEIA-485 Port 2 Slave AddressSet the slave address, 1-254. 0 = disabledEIA-485 Port 3 FunctionSelect Mo
78 LD5200 User Guide 800.518.15194 Web Interface4.3.14 BacnetThe LD5200 can communicate via BACnet. BACnet allows building automation and control dev
rletech.com LD5200 User Guide 794 Web InterfaceFigure 4.31Bacnet PageOption DescriptionBACnet Device NameDesignate a unique name for the LD5200, up t
8 LD5200 User Guide 800.518.1519
80 LD5200 User Guide 800.518.15194 Web Interface4.3.15 Alarm ManagementUse this page to manage and reset current alarms, messages, and alarm history.
rletech.com LD5200 User Guide 814 Web Interface4.3.16 System/Flash ManagementUse this page to update the LD5200’s firmware, the front panel LCD’s fir
82 LD5200 User Guide 800.518.15194 Web Interface4.4 Historical DataThe Historical Data link provides access to logged historical data, including alar
rletech.com LD5200 User Guide 834 Web Interfacecheckbox MM/DD/YY HH:MM:SS. AHxxxx-yy.Alarm history data is also available as a text file (.txt.). Cli
84 LD5200 User Guide 800.518.15194 Web InterfaceThe Trend Log option provides a trending list of logged current leakage. This data provides assistanc
rletech.com LD5200 User Guide 85C HAPTERCHAPT ER 0MODBUS COMMUNICATION5.1 Comm Port SettingsThe Modbus/EIA-485 Configuration Menu allows users to con
86 LD5200 User Guide 800.518.15195 Modbus CommunicationFigure 5.1LD5200 Connection Diagram5.3 Implementation BasicsThe LD5200 is capable of communica
rletech.com LD5200 User Guide 875 Modbus Communication5.3.1.4 Error Check (Checksum) FieldThe checksum field lets the receiving device determine if
88 LD5200 User Guide 800.518.15195 Modbus CommunicationRegister Name Description Units Range40001 Leak Threshold Trip current for leak alarm 25-295 u
rletech.com LD5200 User Guide 895 Modbus Communication5.4.2 Function 04: Read Input RegistersTo read the LD5200 input values, the master must send a
Figuresrletech.com LD5200 User Guide 91 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
90 LD5200 User Guide 800.518.15195 Modbus CommunicationRegister Name Description Units Range30001 Status Bit level status00 : 1 = Leak is Detected01
rletech.com LD5200 User Guide 915 Modbus Communication30024 Modbus Zone7 Distance Location of leak Ft/Meters 0-6553530025 Modbus Zone8 Status Bit Lev
92 LD5200 User Guide 800.518.15195 Modbus Communication30059 Modbus Zone24 Distance Location of leak Ft/Meters 0-6553530060 Modbus Zone25 Status Bit
rletech.com LD5200 User Guide 935 Modbus Communication30094 Modbus Zone41 Distance Location of leak Ft/Meters 0-6553530095 Modbus Zone42 Status Bit L
94 LD5200 User Guide 800.518.15195 Modbus Communication30129 Modbus Zone58 Distance Location of leak Ft/Meters 0-6553530130 Modbus Zone59 Status Bit
rletech.com LD5200 User Guide 955 Modbus Communication30164 Modbus Zone75 Distance Location of leak Ft/Meters 0-6553530165 Modbus Zone76 Status Bit L
96 LD5200 User Guide 800.518.15195 Modbus Communication30199 Modbus Zone92 Distance Location of leak Ft/Meters 0-6553530200 Modbus Zone93 Status Bit
rletech.com LD5200 User Guide 975 Modbus Communication30234 Modbus Zone109 Distance Location of leak Ft/Meters 0-6553530235 Modbus Zone110 Status Bit
98 LD5200 User Guide 800.518.15195 Modbus CommunicationStatus Flags30269 Modbus Zone126 Distance Location of leak Ft/Meters 0-6553530270 Modbus Zone1
rletech.com LD5200 User Guide 995 Modbus Communication5.4.3 Function 06: Preset Single RegisterTo set the LD5200 parameter value, the master must se
Comments to this Manuals